Toshiba CTX28 Telephone User Manual


 
CTX28 Installation
AC Power and Grounding Requirements
1-4 Strata CTX I&M 06/04
AC Power and Grounding Requirements
The CTX28 requires a solid earth ground for proper operation. The AC power cord connects to a
standard AC power outlet. The ground for the CTX28 must originate at the building’s main power
distribution panel and have a solid connection to earth ground. (See Figure 1-2.)
Figure 1-2 Ground to AC Power Cord
CAUTION! Lack of proper ground may cause improper operation and, in extreme cases,
system failure.
WARNING! Failure to provide a proper ground may be a safety hazard to service
personnel or lead to confusing trouble symptoms, such as noise on the talk
path including GVMU greetings and messages. In extreme cases, system
failure may result because the system is not properly protected from
lightning or power transients.
AC Adapter Cord
plugs into GMAS
TB3 on GMAU
Dealer-supplied wire
(#10 AWG gauge or
larger to pass ground
specification test)
CTX28 Cabinet
Grounding Rod
or
Electrical Building
Ground (Main Power
Distribution Box)
AC Voltage
90VAC ± 264VAC
7126
AC Current
1.5 amps max.
TB2
TB1 to HPFB6 FG
(#10 AWG Wire)
P10 Wire Connector
to HPFBG Battery Connector