Toshiba CTX28 Telephone User Manual


 
Rack Mount Cabinets
Changing Plug for Power Strip BRPSB240A
5-30 Strata CTX I&M 06/04
Changing Plug for Power Strip BRPSB240A
You must use a 240VAC power strip (BRPSB240A) if only one AC power cord is connected to a
system with four or more cabinets.
Most 240VAC wall outlets and UPS systems
(ONEAC or other) have twist locks. Twist
locks are mostly used at the wall outlet or UPS
to prevent accidental unplugging.
If you are plugging the Strata rack mount
power strip (BRPSB240A) into a twist lock
outlet/UPS, you will need to change the power
strip plug that exits the cabinets to a twist lock
plug.
Important! Only the 240VAC power strip
that exits the cabinets (see page
5-33) should be changed.
This procedure shows how to change the one
plug on the power strip (shown right).
Recommended parts: Pass & Seymour, L620-P
(NEMA Config. No. L6-20P).
Step 1: Remove NEMA 6-20P from Power Strip
1. Unplug the power strip from the AC.
2. Loosen a screw on both the power plug case and power plug.
3. Slide out the power plug case (shown below).
4. Loosen a screw on the power plug for cable.
Power Strip for
208VAC or 240VAC (only)
BRPSB240A
Receptacle
Pass & Seymour 5858
NEMA No. 6-20P
16A max.
Cable Length 3 m.
(Approx. 9 ft.)
Plug
Pass & Seymour 5466-X
NEMA No. 6-20P
16A max.
6944
Figure 5-13 Power Strip (BRPSB240A)