Mitsubishi Electronics MDS-D2/DH2 Series Pager User Manual


 
Appendix 5 - 17
MDS-D2/DH2 Series Instruction Manual
Appendix 5.6 EMC Countermeasure Parts
< Surge protector for both between phases and between phase and earth >
Features
This surge protector can protect both between phases and between phase and earth.
This contains a fuse and has windows to check malfunction or device degradation.
Specifications
LT-C Series 200V
(Note) Refer to the manufacturer's catalog for details on the surge protector's characteristics and specifications, etc.
LT-C Series 500V
(Note) Refer to the manufacturer's catalog for details on the surge protector's characteristics and specifications, etc.
Outline dimensions
Contact: Soshin Electric Co., Ltd. http://www.soshin-ele.com/
Part name
Circuit
voltage
50/60Hz
Maximum
tolerable
circuit voltage
AC operation
start voltage
(between line
and earth)
AC operation
start voltage
(between
lines)
Voltage
protection
level
(Up)
Nominal
discharge
current
(8/20µs)
Maximum
discharge
current
(8/20µs)
LT-C32G801WS 3AC 250Vrms 275Vrms 560V±20% 410V±20% 1.5kV 2500A 5000A
Part name
Circuit
voltage
50/60Hz
Maximum
tolerable
circuit voltage
AC operation
start voltage
(between line
and earth)
AC operation
start voltage
(between
lines)
Voltage
protection
level
(Up)
Nominal
discharge
current
(8/20µs)
Maximum
discharge
current
(8/20µs)
LT-C35G102WS 3AC 500Vrms 550Vrms 700V±20% 800V±20% 2.0kV 2500A 5000A
Black
Black
Black
Green
Outline dimension drawings
Circuit diagram
Status indicator
Wire (line)
Wire (earth)
[Unit: mm]