Mitsubishi Electronics MDS-D2/DH2 Series Pager User Manual


 
4 - 42
4 Setup
MITSUBISHI CNC
#2236(PR) SV036 PTYP Power supply type/ Regenerative resistor type
MDS-D2/DH2 Series: Power supply type
When connecting a power supply unit, set a code for each power supply unit.
bit F-C : amp
Set the power backup function to be used.
No function used : 0
Deceleration and stop function at power failure : 8
bit B-8 : rtyp
Not used. Set to "0".
bit 7-0 : ptyp External emergency stop setting
When the emergency stop input signal of the power supply unit is "disabled"
Power supply unit is not connected : 00
MDS-D2-CV-37 / MDS-DH2-CV-37 : 04
MDS-D2-CV-75 / MDS-DH2-CV-75 : 08
MDS-D2-CV-110 / MDS-DH2-CV-110 : 11
MDS-D2-CV-185 / MDS-DH2-CV-185 : 19
MDS-D2-CV-300 / MDS-DH2-CV-300 : 30
MDS-D2-CV-370 / MDS-DH2-CV-370 : 37
MDS-D2-CV-450 / MDS-DH2-CV-450 : 45
MDS-D2-CV-550 / MDS-DH2-CV-550 : 55
MDS-DH2-CV-750 : 75
When the emergency stop input signal of the power supply unit is "enabled"
(Note) Set the power supply rotary switch to "4".
Power supply unit is not connected : 00
MDS-D2-CV-37 / MDS-DH2-CV-37 : 44
MDS-D2-CV-75 / MDS-DH2-CV-75 : 48
MDS-D2-CV-110 / MDS-DH2-CV-110 : 51
MDS-D2-CV-185 / MDS-DH2-CV-185 : 59
MDS-D2-CV-300 / MDS-DH2-CV-300 : 70
MDS-D2-CV-370 / MDS-DH2-CV-370 : 77
MDS-D2-CV-450 / MDS-DH2-CV-450 : 85
MDS-D2-CV-550 / MDS-DH2-CV-550 : 95
MDS-DH2-CV-750 : B5
MDS-DM2-SPV Series
Not used. Set to "0000".
External emergency stop power supply type is set by spindle parameter (SP032).
ptyp
rtyp
amp