Mitsubishi Electronics MDS-D2/DH2 Series Pager User Manual


 
5 - 48
5 Servo Adjustment
MITSUBISHI CNC
5.5 Settings for Emergency Stop
Emergency stop in this section refers to the following states.
[1] Emergency stop was input (including other axis alarms)
[2] NC power down was detected
[3] A drive unit alarm was detected
5.5.1 Deceleration Control
With the servo drive unit, if the deceleration stop function is validated, the motor will decelerate following the set time
constant while maintaining the READY ON state. READY will turn OFF and the dynamic brakes will function after
stopping.
If an alarm, for which dynamic brakes are designated as the stopping method, occurs, the motor will stop with the
dynamic brakes.
<Features>
When the load inertia is large, deceleration stop can be executed at a shorter time than the dynamic brakes.
(The stop time for the normal acceleration/deceleration time constants will be achieved.)
(1) Setting the deceleration control time constant
Set the time for stopping from the rapid traverse rate (rapid: axis specification parameter) in the deceleration time
constant for emergency stop (SV056: EMGt). The operation stops with the position loop step when 0 is set.
For the standard setting value of SV056, refer to the following table.
When applying this setting to the synchronous control axes, set the same value with negative symbol to the both
axes. Even if the dynamic break stop is applied to either axis, it is also applied to the other axis.
Standard setting value of SV056
#2004: G0tL G0 time constant (linear)
#2005: G0t1 G0 time constant (primary delay) / Second-step time constant for soft acceleration/deceleration
#2003: smgst Acceleration and deceleration modes
bit 3-0: Rapid traverse acceleration/deceleration type (hexadecimal)
SV056: EMGt Deceleration time constant
at emergency stop
Standard setting value
1:Linear acceleration/deceleration EMGtG0tL× 0.9
8:Exponential acceleration and linear deceleration EMGt(2×G0t1)× 0.9
F:Soft acceleration/
deceleration
#1219:aux03/bit7=0
Accelerating/decelerating time
is G0tL
EMGt(G0tL-G0t1)× 0.9
#1219:aux03/bit7=1
Accelerating/decelerating time
is obtained by G0tL+G0t1
EMGtG0tL× 0.9
A value other than the above EMGtG0tL× 0.9
CAUTION
If the deceleration control time constant at emergency stop (EMGt) is set to a value longer than the above value,
the soft limit point (stroke end point) may be exceeded. Take care as the axis could collide the machine.