RL78/G1A CHAPTER 11 A/D CONVERTER
R01UH0305EJ0200 Rev.2.00 391
Jul 04, 2013
(1) If an interrupt is generated after A/D conversion ends
If the A/D conversion result value is inside the range of values specified by the A/D conversion result comparison
function (which is set up by using the ADRCK bit and ADUL/ADLL register), the A/D conversion end interrupt request
signal (INTAD) is generated.
While in the select mode
When A/D conversion ends and an A/D conversion end interrupt request signal (INTAD) is generated, the A/D
converter returns to normal operation mode from SNOOZE mode. At this time, be sure to clear bit 2 (AWC = 0:
SNOOZE mode release) of the A/D converter mode register 2 (ADM2). If the AWC bit is left set to 1, A/D
conversion will not start normally in the subsequent SNOOZE or normal operation mode.
While in the scan mode
If even one A/D conversion end interrupt request signal (INTAD) is generated during A/D conversion of the four
channels, the clock request signal remains at the high level, and the A/D converter switches from the SNOOZE
mode to the normal operation mode. At this time, be sure to clear bit 2 (AWC = 0: SNOOZE mode release) of A/D
converter mode register 2 (ADM2) to 0. If the AWC bit is left set to 1, A/D conversion will not start normally in the
subsequent SNOOZE or normal operation mode.
Figure 11-35. Operation Example When Interrupt Is Generated After A/D Conversion Ends (While in Scan Mode)
ADCS
Interrupt signal
(INTAD)
INTRTC
Clock request signal
(internal signal)
Conversion
channels
Channel 1 Channel 2 Channel 3 Channel 4
An interrupt is generated
when conversion on one
of the channels ends.
The clock request signal
remains at the high level.
Clearing AWC bit to 0