Page 452 of 488 Installing and cross-connecting a Power Fail Transfer Unit
553-3041-210 Standard 4.00 September 2007
End of Procedure
Connecting a trunk to a PFTU
Follow Procedure 117 to connect a Trunk to a PFTU.
Procedure 117
Connecting a Trunk to a PFTU
1 Locate the PFTU terminal blocks at the cross-connect terminal.
2 Cross-connect the first pair of the assigned PFTU to the telephone.
See Table 59 on page 453 for PFTU connections.
3 Cross-connect the second pair of the PFTU to the TN assigned to the
telephone.
4 Cross-connect the third pair of the PFTU to the Central Office trunk.
5 Cross-connect the third pair of the PFTU to the TN assigned to the trunk.
PFT 5
21T
21R
V-BL
BL-V
Telephone
22T
22R
V-O
O-V
Telephone Line card
23T
23R
V-G
G-V
Central Office Trunk
24T
24R
V-BR
BR-V
Trunk Line card
Table 58
Power Fail Transfer Unit connections (Part 3 of 3)
QUA6 J1 Cable
Function Pair Color Connects to: