7-2. Outdoor Unit
7-2-1. Applied Control in Outdoor Unit
The following functions become available by setting the switches on the outdoor interface P.C. board.
No.
1
Function
Outdoor fan high static pressure shift
Switch No.
SW10
Bit
2
Interface P.C. board of outdoor unit
SW10
Bit 2
For setup of outdoor fan high static pressure shift
Switch position detail
7-2-1-1. Outdoor fan High Static Pressure Shift
n Usage/Features
This function is set when connecting a duct to the discharge port of the outdoor unit.
n Setup
Tu r n Bit 2 of the dip switch [SW10] on the interface P.C. board of the outdoor unit to ON.
n Specifications
The outdoor fan high static pressure shift function increases the fan speed on the outdoor unit to enable a
discharge duct to be installed on the discharge port - the design of the ducting should be such that a static
pressure of 35 Pa is not exceeded.
This function should be executed where the discharge ducting static pressure exceeds 15 Pa.
45Pa or more : For detail of adjustment, consult with the sales subsidiary.
The discharged air volume from each outdoor unit is shown in the table below:
Capacity rank (MMY-MAP)
Standard air volume of outdoor unit (m³/min.)
0801 type 1001, 1201 type
165 175