Toshiba MMU-AP0091H Two-Way Radio User Manual


 
136
Check code
Outdoor 7-segment display
Display on
central control
device
Check code Sub-code
AI-NET
central control
remote controller
Detected position Check code name Status
Error detection
condition
Check item (position)
C05 ——TCC-LINK TCC-LINK central control
device transmission error
Operation
continued.
Signal is not transmit from
central control device.
Check central control device error.
Check communication line error of central control device.
Check setup of terminator resistor.
C06 ——TCC-LINK central control
device receiving error
Operation
continued.
Si
g
nal is not received from
central control device.
Check central control device error.
Check communication line error of central control device.
Check setup of terminator resistor.
Check the power of connecting destination connected device.
Check P.C. board error of the connected device.
C12 ——HA control interface Interface batch alarm of
HA control interface
Operation
continued.
Error was input in HA
control interface
Check error input.
Differs according to error contents of the with alarm
TCC-LINK Follower unit error of
group control
Operation
continued.
An error occurred in
follower unit of the group
control.
([P30] is displayed only on
the central remote
controller.)
Check the error code of the unit with alarm.
P30
(L20 is displayed.) Duplicated central control
address
Operation
continued.
Central control addresses
were duplicated.
Check the address setup.
Check code
Outdoor 7-segment display
Main remote
controller
Check code Sub-code
AI-NET
central control
remote controller
Detected position Check code name Status
Error detection
condition
Check item (position)
——— 97 AI-NET AI-NET communication
system error
Operation
continued.
E07/L07/L03/L08 was
detected when other
indoor unit in the group
was defective.
Check multiple network adapters.
Check wire and miscabling of remote controller: Only one network
adapter can be connected to communication line of remote controller.
——— 99 AI-NET Duplicated network
adapters
Operation
continued.
Multiple network adapters
were connected to
communication line of
remote controller.
(Detected at central
controller side)
Check communication line, miscabling, and power of indoor unit.
Check communication. (X, Y terminals)
Check network adapter P.C. board.
Check the central controller (Central control remote controller, etc.)
——— b7 AI-NET Error in indoor group Operation
continued.
Error of follower unit in the
group
Check follower unit in the group.
Error detected by TCC-LINK central control device
Error detected by AI-NET central control device
* These errors are concerned to communication of remote controllers (A, B) and central system [AI-NET X, Y], and the main remote controller displays [E01], [E02], [E03], [E09],