Toshiba MMU-AP0091H Two-Way Radio User Manual


 
132
Check code
Outdoor 7-segment display
Main
remote
controller
Check code Sub-code
AI-NET
central control
remote controller
Detected
position
Check code
name
Status Error detection condition Check item (position)
P01 —— 11 Indoor Indoor fan
motor error
Correspondin
g
unit only stops.
Check the lock of fan motor (AC fan).
Check cabling.
P03 P03 1E I/F Discharge
temp TD1
error
All stop Discharge temp (TD1)
exceeded 115°C.
Check full opening of outdoor service valves (Gas side, Liquid side).
Check clogging of outdoor PMV. (PMV1,2)
Check characteristics of TD1 sensor resistance value.
Check refrigerant shortage.
Check 4-way valve error.
Check leakage of SV41 circuit.
Check SV4 circuit. (Miswiring and misinstallation of SV41 and SV42)
Check leakage of SV5 circuit.
Check leakage of SV6 circuit. (Capillary clogging, valve operation error)
Check mispiping of discharge gas/suction gas main pipe.
Check Flow selector unit.
Check leakage of SVD valve and SVS valve.
(Check leakage of SVDD valve and SVSS.)
Check mispiping of FS unit connecting pipe (Suction gas/Discharge gas), wiring
between FS unit and indoor unit, and connection of connectors.
Check miswiring of SVS/SVD valves.
P04 P04 01: Compressor 1 side
02: Compressor 2 side
21 I/F
Actuation of
high-pressure
SW
All stop High-pressure SW actuated. Check Pd pressure sensor error.
Check full opening of outdoor service valves (Gas side, Liquid side).
Check outdoor fan error.
Check outdoor fan motor error.
Check clogging of outdoor PMV. (PMV1,2)
Check clogging of indoor/outdoor heat exchangers.
Check short-circuiting of outdoor suction/discharge air.
Check clogging of SV2 circuit.
Check outdoor P.C. board (I/F) error.
Check indoor fan system error. (Cause of air volume decrease)
Check opening of indoor PMV.
Check miscabling of communication line between indoor and outdoor.
Check operation error of check valve of discharge pipe.
Check SV4 valve circuit.
Check SV5 valve circuit.
Check refrigerant overcharge.
Check mispiping of discharge gas/suction gas main pipe.
Check circuit clogging at auxiliary heat exchanger side. (PMV3, SV12, check valve)
Check FS unit.
Check clogging of SVD valve and operation error.
Check wiring inside of FS unit. (SVD/SVS coil miswiring, etc.)
Check wiring between FS unit and indoor unit.
(Miswiring, Disconnection, Wiring missing)
P05 P05 01: Power supply
missing phase
02: Power supply
phase order
(reversed phase)
AF I/F Phase missin
g
or reversed
phase order
All stop Missin
g
phase was detected
when the power turned on.
Reversed phase was
detected when the power
turned on.
Check outdoor power line.
Check outdoor P.C. board (I/F) error.