(*1) All stop only in case of the header unit The follower unit continues operation.
MG-SW : Magnet Switch, OCR : Over-current Relay
Check code
Outdoor 7-segment display
Main
remote
controller
Check code Sub-code
AI-NET
central control
remote controller
Detected
position
Check code name Status Error detection condition Check item (position)
F13 F13 01: Compressor 1 side
02: Compressor 2 side
43 IPDU TH sensor error All stop Resistance value of sensor is
infinite or zero (Open/Short).
IGBT built-in temp sensor error
Exchange IPDU P.C. board.
F15 F15 18 I/F Outdoor temp sensor
miscabling (TE1, TL)
All stop During operation of
compressor in HEAT mode, the
TE1 detection temp was hi
g
her
than that of TL by the specified
value continued for 3 minutes
or more.
Check installation of TE1 sensor and TL sensor.
Check characteristics of TE1 and TL sensor resistance value.
Check outdoor P.C. board (I/F) error.
F16 F16 43 I/F Outdoor pressure
sensor miscabling
(Pd, Ps)
All stop High-pressure Pd sensor and
low-pressure Ps sensor were
exchanged, or output voltages
of both sensors are zero.
Check connection of high-pressure Pd sensor connector.
Check connection of low-pressure Ps sensor connector.
Check pressure sensors Pd and Ps error.
Check outdoor P.C. board (I/F) error.
Check compression error of compressor.
F23 F23 43 I/F Ps sensor error All stop Output voltage of Ps sensor
was zero.
Misconnection of Ps sensor and Pd sensor connectors
Check connection of Ps sensor connector.
Check Ps sensor error.
Check compression error of compressor.
Check 4-way valve error.
Check outdoor P.C. board (I/F) error.
Check SV4 circuit error.
F24 F24 43 I/F Pd sensor error All stop Output volta
g
e of Pd sensor
was zero. (Sensor Open)
Pd > 4.15MPa during stop of
compressor
Check connection of Pd sensor connector.
Check Pd sensor error.
Check outdoor P.C. board (I/F) error.
F29 —— 12 Indoor Indoor other error
Correspondin
g
unit only stops.
Indoor P.C. board did not
operate normally.
Check indoor P.C. board error (EEPROM error).
F31 F31 1C I/F Outdoor EEPROM error All stop (*1)
Outdoor P.C. board (I/F) did not
operate normally.
Check power voltage.
Check power noise.
Check outdoor P.C. board (I/F) error.
H01 H01 01: Compressor 1 side
02: Compressor 2 side
1F IPDU Compressor breakdown All stop
Inverter current detection circuit
detected over-current and
stopped.
Check power voltage. (AC220240V ± 10%).
Check compressor error.
Check cause of abnormal overload operation.
Check outdoor P.C. board (IPDU) error.
H02 H02 01: Compressor 1 side
02: Compressor 2 side
1d IPDU Compressor error (lock)
MG-SW error
OCR operation
All stop Over-current was detected
several seconds after header
compressor had started.
Check compressor error.
Check power voltage. (AC38010%, 415V +10%).
Check cable of compressor and phase-missing.
Check connector/terminal connection on IPDU P.C. board.
Check conduction of case heater.
(Check activation error due to liquid stagnation in compressor.)
Check outdoor P.C. board (IPDU) error.
Check outdoor MG-SW or OCR.