7-1-3. Setting When Connecting Multiple Indoor Units to a FS unit
Cautions to connection of indoor unit
• When connecting multiple indoor units to a single FS unit, it is necessary to set up the Item code.
This should be done after the addressing of the units.
• When connecting multiple indoor units to a single FS unit, only group control is available.
Remote controllers cannot be connected to individual units.
n Usage/Features
It is not possible to group control indoor units that
are connected to more than one FS unit.
Indoor units off of a single FS unit cannot be indi-
vidually controlled.
How to set up Item code
1
Push
VENT
+
TEST
buttons simultaneously for
4 seconds or more.
• is displayed in the UNIT No. window.
• At this time, the fans of all the indoor units in
the group control start the fan operation.
2
Using the set temperature buttons /
, select the Item code “- ”.
3
Change SET DATA to “ ” using the timer
buttons
/ .
4
Push
SET
button.
5
Push
TEST
button.
This confirms the setup has finished.