Toshiba MMU-AP0091H Two-Way Radio User Manual


 
72
Table: Function selecting item code (DN)
(Items necessary to perform the applied control at the local site are described.)
DN
01
02
03
04
06
0d
0E
0F
10
11
12
13
14
19
1E
28
29
2A
2E
30
31
32
33
40
5d
60
62
Item
Filter display delay
timer
Dirty state of filter
Central control
address
Specific indoor unit
priority
Heating temp shift
Existence of [AUTO]
mode
Follows operation
mode of the header
unit
Cooling only
Type
Indoor unit capacity
Line address
Indoor unit address
Group address
Louver type
(Adjustment of air
direction)
Temp difference of
[AUTO] mode
selection COOL
HEAT, HEAT COOL
Automatic restart of
power failure
Operation condition
of humidifier
Selection of option/
error input (CN70)
HA terminal (CN61)
select
Automatic elevating
grille
Ventilating fan
control
TA sensor selection
Temperature unit
select
Drain pump control
High ceiling selection
(Air volume selection)
Timer set
(Wired remote
controller)
Anti-ceiling
smudging control
Description
0000 : None 0001 : 150H
0002 : 2500H 0003 : 5000H
0004 : 10000H
0000 : Standard
0001 : High degree of dirt (Half of standard time)
0001 : No.1 unit to 0064 : No.64 unit
0099 : Unfixed
0000 : No priority 0001 : Priority
0000 : No shift 0001 : +1°C
0002 : +2°C to 0010 : +10°C
(Up to +6 recommended)
0000 : Provided
0001 : Not provided (Automatic selection from connected outdoor unit)
0000 : Does not follow
0001 : Follows
0000 : Heat pump
0001 : Cooling only (No display of [AUTO] [HEAT])
0000 : (1-way air discharge cassette)
0001 : (4-way air discharge cassette) to 0037
0000 : Unfixed 0001 to 0034
0001 : No.1 unit to 0030 : No.30 unit
0001 : No.1 unit to 0064 : No.64 unit
0000 : Individual 0001 : Header unit of group
0002 : Follower unit of group
0000 : Not provided 0001 : Swing only
0004 : [4-way Air Discharge Cassette type] and [Under Ceiling type]
0000 : 0 deg to 0010 : 10 deg
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 : None 0001 : Restart
0000 : Usual 0001 : Condition ignored
(Detection control for heat exchanger temperature)
0000 : Filter input 0001 : Alarm input (Air washer, etc.)
0002 : None
0000 : Usual 0001 : Leaving-ON prevention control
0000 : Unavailable 0001 : Available
0000 : Unavailable 0001 : Available
0000 : Body TA sensor 0001 : Remote controller sensor
0000 : °C (at factory shipment)
0001 : °F
0000 : None 0001 : Pump ON
0002 : None 0003 : Pump OFF
[4-way Air Discharge Cassette type] and [Under Ceiling type]
0000 : Standard filter 0001 : Super-long life filter
0003 : High efficiency filter
[Concealed Duct Standard type]
0000 : Standard static pressure (40Pa)
0001 : High static pressure 1 (70Pa)
0003 : High static pressure 2 (100Pa)
0005 : Correspond to quiet sound
0006 : Low static pressure (20Pa)
0000 : Available (Operable)
0001 : Unavailable (Operation prohibited)
0000 : Clear
At shipment
According to type
0000 : Standard
0099 : Unfixed
0000 : No priority
0002 : +2°C
(Floor type 0000: 0°C)
0001 : Not provided
0000 : Not provided
0000 : Heat pump
According to model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
According to type
0003 : 3 deg
(Ts±1.5)
0000 : None
0000 : Usual
0002 : None
0000 : Usual
(HA terminal)
0000 : Unavailable
0000 : Unavailable
0000 : Body TA sensor
0000 : °C
0003 : Pump OFF
0000 : Standard
0000 : Available
4- way Air Discharge
Cassette type only