Toshiba MMU-AP0091H Two-Way Radio User Manual


 
129
Check code
Outdoor 7-segment display
Main
remote
controller
Check code Sub-code
AI-NET
central control
remote controller
Detected
position
Check code name Status Error detection condition Check item (position)
H07 H07 d7 I/F Protection for oil
level drop detection
All stop The operating compressor
detected oil shortage
continuously for 2 hours.
Check all the outdoor units in the corresponding line.
Check full opening of service valve of balance pipe.
Check connection and installation of TK1, TK2, TK3, and TK4 sensors.
Check characteristics of TK1, TK2, TK3, and TK4 resistance values.
Check gas leak and oil leak in the same line.
Check refrigerant stagnation in compressor.
Check error of SV3A, SV3B, SV3C, SV3D, and SV3E valves.
Check clogging of oil separator oil return circuit.
Check clogging of oil-equation circuit.
<Check clogging of oil equation pipe between compressors.>
Check TS1, TS2 sensors (Miswiring and misinstallation of TS1 and TS2)
Check leakage of SV6 circuit.
Check FS unit.
Leakage of check valve of bypass between liquid pipe and discharge gas pipe
Mispiping of discharge/suction gas connection
Miswiring of SVD/SVS valve/Misinstallation of coil
Check whether there is no setup missing of indoor unit in all cooling operation mode
All stop Resistance value of
sensor is infinite or zero.
(Open/Short)
Check connection of TK1 sensor connector.
Check characteristics of TK1 sensor resistance value.
Check outdoor P.C. board (I/F) error.
All stop Resistance value of
sensor is infinite or zero.
(Open/Short)
Check connection of TK2 sensor connector.
Check characteristics of TK2 sensor resistance value.
Check outdoor P.C. board (I/F) error.
All stop Resistance value of
sensor is infinite or zero.
(Open/Short)
Check connection of TK3 sensor connector.
Check characteristics of TK3 sensor resistance value.
Check outdoor P.C. board (I/F) error.
H08 H08
01: TK1 sensor error
02: TK2 sensor error
03: TK3 sensor error
04: TK4 sensor error
d4 I/F Oil level detective
temp sensor error
All stop Resistance value of
sensor is infinite or zero.
(Open/Short)
Check connection of TK4 sensor connector.
Check characteristics of TK4 sensor resistance value.
Check outdoor P.C. board (I/F) error.
H14 H14 44 I/F Compressor 2
case thermo
operation
All stop Compressor 2 case
thermostat operated.
Check compressor 2 case thermo circuit. (Connector, cable, P.C. board)
Check full opening of service valve. (Gas and liquid side)
Check outdoor PMV clogging. (PMV1, 2)
Check SV42 valve leak.
Check miscabling/misinstallation of SV41 and SV42.
Check valve opening of indoor PMV.
Check 4-way valve error.
Check refrigerant shortage.
Check SV11 circuit. (Wiring, OFF at one side only)
Check mispiping of discharge gas/suction gas main pipe.
Check Flow selector unit.
Check leakage of SVD valve and SVS valve. (Check leakage of SVDD valve and SVSS.)
Check mispipin
g
of FS unit connectin
g
pipe
(
Suction
g
as/Dischar
g
e
g
as
)
, wirin
g
between
FS unit and indoor unit, and connection of connectors.
Check miswiring of SVS/SVD valves.