INSTALLATION-DK16 KSU & PCB
SECTION 100-816-205
MARCH 1993
5-10
13) Knock out the tab on the bottom of the side
cover.
14) Plug the AC power cable into an outlet and
then turn ON the power supply switch.
15) Install the side cover to the Expansion Key
Service Unit (Figure 5-7).
2.40 Reserve Power/Power Failure Options
2.41 The STRATA DK systems offer two options
to protect system operation in the event of a power
failure; the Reserve Power option (Paragraph 2.42-
2.44), and the Power Failure Emergency Transfer
option (Paragraph 17).
2.42 Reserve Power Option STRATA DK16 sys-
tem power supply provides the capability of con-
necting a reserve power source (two customer
supplied 12-volt batteries) to ensure uninterrupted
system operation in the event of a power failure. A
pre-assembled interface cable for installation of
the Reserve Power option is available from Toshiba
(PBTC-3M), refer to Figure 5-9.
IMPORTANT NOTE!
Local ordinances may dictate battery type
and installation details.
2.43 The batteries require a well-ventilated loca-
tion close (within 9 feet) to the system —the
interface cable is 9 feet long.
WARNING!
To reduce the risk of fire or injury to
persons, read and follow these instruc-
tions:
1. Use only the following type and size
batteries: 12-volt, gelcell.
2. Do not dispose of the batteries in a fire.
The cells may explode. Check with
local codes for possible special dis-
posal instructions.
3. Do not open or mutilate the batteries.
Released electrolyte is corrosive and
may cause damage to the eyes or skin.
It may be toxic if swallowed.
4. Exercise care in handling batteries in
order not to short the battery with con-
duction materials such as rings, brace-
lets, and keys. The battery or conduc-
tor may overheat and cause burns.
5. Charge the batteries provided with or
identified for use with this product
only in accordance with the instruc-
tions and limitations specified in this
manual.
6. Observe proper polarity orientation
between the batteries and battery
charger.
2.44 Reserve Power Installation. Install the Re-
serve Power option in accordance with the follow-
ing steps (refer to Figure 5-9):
1) Connect the PBTC-3M black jumper wire
from the positive terminal of one 12VDC
battery to the negative terminal of the second
12VDC battery.
2) Ensure that a serviceable 10-ampere fuse is
installed in the in-line fuse holder of the PBTC-
3M battery cable.
3) Connect the white lead of the PBTC-3M bat-
tery cable to the open positive terminal of the
12VDC battery. Connect the black lead to the
open negative terminal of the second 12VDC
battery.
IMPORTANT NOTE!
The KSU must be connected to the live
operating (HOT) AC power source, and
the power supply ON/OFF switch set to
ON prior to the final step of connecting the
reserve power batteries to the power sup-
ply via the BATT +/- receptacle. If the
batteries are connected after AC power is
lost, reserve power will not function.
4) Connect the PBTC-3M battery cable two-
prong male plug to the power supply BATT +/
- receptacle.
5) To test reserve power operation, disconnect
the system AC power plug with the power
supply power ON/OFF switch in the ON posi-
tion. The system should continue to operate
without any interruption.