Toshiba DK 16 Telephone User Manual


 
REMOTE ADMINISTRATION AND MAINTENANCE PROCEDURES
SECTION 100-816-600
MARCH 1993
-22-
IMPORTANT NOTES:
1. This program only applies to DK16 and must be completed with on-site assistance (after
installing PCBs, if any) because the system must be powered down momentarily after PCB
code entry.
2. Even though PCB codes display as being changed, they are not entered into working
memory until the system DC power is cycled OFF and ON.
3. If PCB codes are not entered into working memory by cycling DC power, PCB options will
not function.
4. Only
Program 03
requires the system power to be turned OFF and ON to store data into
working memory.
To store data, press CR.
Continue returning to Step 3 until all
data is entered.
To exit this program, press # #, press CR.
TABLE RM-K
PROGRAM 03
SLOT ASSIGNMENTS
ACTIONSTEP DISPLAY/PRINTOUT
1
>MODE PROG
P
Enter the Program Mode
At the >MODE prompt, enter P R O G CR.
2 P 03
P03
Enter Program Number 03
Press CR.
3 P03
P03 00 91
Enter the Slot Number
Refer to the System Record Sheet and enter the desired
slot number.
Example: Slot number 00, enter 0 0.
4 P03
P03 00 91 92
Enter the PCB Code Number
5 P03
P03 00 91 92
P03 ##
P
To Exit Program/Store Data
Refer to the System Record Sheet and enter the desired
PCB code number.
Example: PCB code 92, enter 9 2.
A)
B)
C)
6 Turn system power "OFF" for 5 seconds and then turn
power "ON" to store data in working memory (see Notes).
Remote maintenance is disconnected.
Program 03