Lucent Technologies Release 3 Telephone User Manual


 
2-42 Issue 1 June 2000
Task 22 - Activate Alarm Origination
The following procedure creates an acceptance test that verifies and sends a
message to the remote maintenance center. This test demonstrates that the
connection is good, the system is prepared to automatically transmit alarms, and
the designated remote maintenance center is ready to accept alarms for this
system. This procedure tests the path from the Lucent INTUITY system to the
remote maintenance center.
1. Starting at the Customer/Services Administration screen, select:
The system displays the Alarm Management screen (Figure 2-21).
2. Determine your next step:
If the Product ID and Alarm Destination fields are administered,
continue with Step 3.
If the Product ID and Alarm Destination fields are not administered,
enter the information now. After entering the information, continue
with Step 3.
Figure 2-21. Alarm Management Screen
3. Move the cursor to the Alarm Origination field.
4. Press (Choices).
The system displays the Alarm Origination screen (Figure 2-22).
> Alarm Management
F2