Cutler-Hammer K-2000 Telephone Accessories User Manual


 
Effective December, 1998
IL 33-K2C-1
Page 13
NOTE: If specified during ordering, special
Trip Unit Mounting Brackets (taller then the
standard brackets) have been supplied for
some older models of the KDON-1600 Black
Breaker equipped with trigger fuses. If the
Brackets are needed but were not ordered,
contact Cutler-Hammer at 1-800-937-5487.
C. Mount the left Trip Unit Mounting Bracket to the
Trip Unit Assembly using (2) .190-32 × .375" flat
head screws supplied.
D. Set the Trip Unit Assembly on the Breaker
Platform with the holes on the right side in line
with the Mounting Bracket holes.
E. Mark the Breaker Platform through the slots in
the bottom left Mounting Bracket. Remove the
Trip Unit Assembly.
F. Assure that the area under the Breaker Platform
where the holes will be drilled is clear, then drill
two (2) 0.166" diameter holes where marked.
G. Remove the left hand Mounting Bracket from
the Trip Unit Assembly. Install the Mounting
Bracket on the Breaker Platform using the (2)
.190-18 × .500" thread cutting screws, (2) lock
washers, and (2) flat washers supplied.
H. Mount the Trip Unit Assembly to the Mounting
Brackets using the (4) .190-32 × .375" flat head
screws supplied.