Delta DVP-ES2/EX2/SS2/SA2/SX2/SE Two-Way Radio User Manual


 
DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual - Programming
2-22
Special
M
Function
ES2
EX2
SS2 SA2 SX2
OFF
Ø
ON
STOP
Ø
RUN
RUN
Ø
STOP
Attrib.
Latch
-ed
Default
M1141
For COM2 (RS-485), MODRD / MODWR
/ MODRW parameter error
OFF OFF - R NO OFF
M1142
Data receiving error of VFD-A handy
instructions
OFF OFF - R NO OFF
M1143*
For COM2(RS-485), ASCII/RTU mode
selection (OFF: ASCII; ON: RTU)
OFF - - R/W NO OFF
M1156*
Enabling the mask and alignment mark
function on I400/I401(X4) corresponding
to Y0
OFF OFF - R/W NO OFF
M1158*
Enabling the mask and alignment mark
function on I600/I601(X6) corresponding
to Y2
OFF OFF - R/W NO OFF
M1161 8/16 bit mode (ON = 8 bit mode)
OFF - - R/W NO OFF
M1162
Switching between decimal integer and
binary floating point for SCLP instruction.
ON: binary floating point; OFF: decimal
integer
OFF - - R/W NO OFF
M1167 16-bit mode for HKY input
OFF - - R/W NO OFF
M1168 Designating work mode of SMOV
OFF - - R/W NO OFF
M1177
Enable the communication instruction for
Delta VFD series inverter.
ON: VFD-A (Default), OFF: other models
of VFD
OFF - - R/W NO OFF
M1178 Enable knob VR0
OFF - - R/W NO OFF
M1179 Enable knob VR1
OFF - - R/W NO OFF
M1182
M1182 = ON, disable auto-mapping
function when connected with left-side
modules.
For SA2 /SX2 models, values of AIO
modules will be auto-mapped to
D9800 and above.
If the left side is connected with a
communication module, additional 10
words will be occupied. Ex: 04AD-SL
+ EN01-SL + SA2, average value of
Ch1~Ch4 of 04AD-SL maps to
D9810~D9813.
OFF - - R/W NO OFF
M1183
M1183 = ON, disable auto mapping
function when connected with special
modules
#: ES2/EX2: OFF; SS2/SA2/SX2: ON
(maps to D9900 and above)
# - - R/W NO #
M1190
Set Y0 high speed output as 0.01 ~
100Hz
OFF OFF - R/W NO OFF
M1191 Set Y1 high speed output as 0.01 ~ 100Hz
OFF OFF - R/W NO OFF
M1192 Set Y2 high speed output as 0.01 ~ 100Hz
OFF OFF - R/W NO OFF
M1193 Set Y3 high speed output as 0.01 ~ 100Hz
OFF OFF - R/W NO OFF
M1200 C200 counting mode (ON: count down)
OFF - - R/W NO OFF
M1201 C201 counting mode (ON: count down)
OFF - - R/W NO OFF
M1202 C202 counting mode ON: count down)
OFF - - R/W NO OFF