System and Control Options
70
9.9.3 Setup Site ID
You may enter a Site ID to identify the Universal Monitor’s location,
using a name that may consist of up to 40 characters (see Table 20 for
valid characters). The Site ID will appear with each alarm.
To enter or change the Site ID:
• From the Setup System Info Menu, use the arrows
↑↓ to choose
Setup Site ID, then press Enter ↵ .
• To enter a Site ID:
• Use the arrows
↑↓ to choose a character.
• Press Enter ↵ to advance to the next character position.
• If the Site ID is less than 40 characters, you may enter an
underscore (_) character to indicate the end of the name.
• When finished, press Enter ↵ again.
9.9.4 Connect Battery
By default, the Universal Monitor checks the battery and sounds an alarm when the power fails, the
battery runs low or the battery needs to be checked. The battery’s main purpose is to provide enough
power to the modem to notify pagers of a power loss.
Using the following procedure to disconnect the battery will disable battery alarm features only. The
battery itself will continue to provide backup. If battery backup is not desired, the battery must be
unplugged from the circuit board. This can be done by removing the battery leads from the jumpers
(see 2.4.3 - Connecting the Battery Pack).
The default is to connect the battery. However, there may be times that you want to disconnect the
battery so that it does not provide backup.
Table 31 shows battery problems that will affect operation.
To connect or disconnect the battery:
• From the Setup System Info Menu, use the arrows
↑↓ to choose
Connect Battery, then press Enter ↵ .
• Use the arrows
↑↓ to choose Y (Yes - the battery is connected) or
N (No - the battery is not connected), then press Enter ↵.
NOTE
The battery will continue to power and provide full operation of the Universal Monitor with the
exception of powering the analog inputs (sensors). The battery will provide backup for a
minimum of 10 minutes.
Table 31 Battery alarms
Result of Battery Action Message Generated
Battery falls below a minimum charge. Battery will not provide battery backup. LOW BATTERY
Battery is connected to the circuit board but
not recognized by the circuit board.
Battery will not provide battery backup. CHECK BATTERY
Battery is unplugged from the circuit board. Battery will not provide battery backup BATTERY UNPLUGGED
Utility power (24VAC) to the circuit board is
too low to power the board.
Universal Monitor board will not be
able to function properly.
LOSS OF POWER
Setup System Info Menu
SETUP SYSTEM INFO
CHANGE PASSWORD
CHANGE DATE & TIME
↑↓=NEXT ↵ =SELECT
> SETUP SITE ID
CONNECT BATTERY
SETUP SERV PH NUM
FACTORY DEFAULTS
Setup Site ID
SETUP SITE ID
AAAAAAAAAAAAAAAAAAAA
AAAAAAAAAAAAAAAAAAAA
↑↓=SELECT ↵ =NEXT/END
Setup System Info Menu
SETUP SYSTEM INFO
CHANGE PASSWORD
CHANGE DATE & TIME
↑↓=NEXT ↵ =SELECT
SETUP SITE ID
> CONNECT BATTERY
SETUP SERV PH NUM
FACTORY DEFAULTS
Connect Battery
IS THE BATTERY
CONNECTED? Y
↑↓=Y/N ↵=END