System and Control Options
64
9.8.3 Pager Setup - Pager Number and PIN
The Universal Monitor may be configured to dial numeric or alphanumeric pagers when an alarm is
detected. You may enter up to four pager numbers—all configured pagers will be dialed each time an
alarm occurs. For each configured pager, you must enter the pager number to be dialed and the
pager’s Personal Identification Number (PIN).
See 10.1 - Universal Monitor Specifications for supported pager settings.
The Universal Monitor can send numeric or alphanumeric messages to supported pagers, as shown in
the following example:
When an alarm is detected, the first pager number is dialed—up to three times, if needed. After a suc-
cessful page or three dialing attempts, the next pager number is dialed, again with three attempts as
needed, and so on for all configured pagers.
To configure a pager:
Log In and Choose Setup System
• From the Main Menu, use the arrows
↑↓ to choose System and
Control, then press Enter ↵ (see 9.1 - Login for help).
• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows
↑↓ to choose
Setup System, then press Enter ↵ .
Select a Pager to Configure
• From the Setup System Menu, shown at right, use the arrows
↑↓
to
choose Setup Modem&Pagers and press Enter ↵ .
• Use the arrows
↑↓ to choose Setup Pagers from the Pagers &
Modem Menu, and press Enter ↵ .
• From the Select Pager Menu, choose the pager number you
want—for example, Pager Number 1—and press Enter ↵ .
Alphanumeric pager
message example
LIEBERT TEST
INPUT_01 ALARM
CONTACT CLOSED
2:07 PM 06/09/04 Pager company time stamp
Table 29 Pager dialing results
Result of Page Action Message Generated
Successful Universal Monitor dials next configured pager. —
Unsuccessful due to:
Busy signal / no answer /
no dial tone
Universal Monitor generates message after all three
redial attempts have failed, dials next configured pager.
Unsuccessful Page
(Event Log)
General modem
communication problem
Universal Monitor resets modem, generates
message, redials pager up to three more times.
Modem Reset
(Event Log)
No communication with modem
(internal hardware problem)
Universal Monitor generates messages, makes no
further dialing attempts.
Modem Internal Fault
(Active Alarm Report,
Alarm History Log)
Setup System Menu
SETUP INPUT
SETUP COMMON ALARM
SETUP SENSOR
SETUP I/O MATRIX
↑↓=NEXT ↵ =SELECT
SETUP OUTPUT
> SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP EXP BOARD
Pagers & Modem Menu
> SETUP PAGERS
SETUP MODEM
↑↓=NEXT
↵ =SELECT
Select Pager Menu
SELECT PAGER
> PAGER NUMBER 1
PAGER NUMBER 2
↑↓=NEXT ↵ =SELECT
PAGER NUMBER 3
PAGER NUMBER 4