Default Settings Quick Reference Guide
132
APPENDIX B- DEFAULT SETTINGS QUICK REFERENCE GUIDE
This appendix provides a quick reference to default settings for the Universal Monitor and the
optional Expansion Board. These settings also appear throughout the manual.
Table 37 Universal Monitor - default settings for inputs and outputs
DEFAULT SETTINGS - DIGITAL INPUTS (FROM TABLE 21)
Feature Default Other Options
LABEL INPUT_01 - INPUT_08 Any name (up to eight characters)
NORM OPEN/CLOSE NO (Normally open) NC (Normally closed)
ALARM/EVENT AL (Alarmable) EV (Event)
LATCHED NL (Unlatched) / N (No)* L (Latched) / Y (Yes)*
DELAY 00:01 (1 second) Any time (in minutes and seconds) from 00:00 to 99:59
* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched.
DEFAULT SETTINGS - ANALOG SENSOR INPUTS (FROM TABLE 22)
Feature Default Other Options
CONNECTED* N (Not connected)* Y (Connected)**
LABEL SENSOR_1 - SENSOR_4 Any name (up to eight characters)
UNITS Blank Any units (up to three characters)
4 mA -999.9 Can define up to two decimal places—e.g., -99.99
20 mA +999.9 Can define up to two decimal places—e.g., +99.99
OFFSET +000.0 Can define up to two decimal places—e.g., +00.00
ALARM/EVENT AL (Alarmable) EV (Event)
LATCHED N (Unlatched) Y (Latched)
LOW SETPT -0999.9 Can define up to two decimal places—e.g., -999.99
HIGH SETPT +0999.9 Can define up to two decimal places—e.g., +999.99
SENSOR DELAY 00:01 (1 second) Any time (in minutes and seconds) from 00:00 to 99:59
* If a sensor is configured as N (Not connected), the display will show an empty reading (blank spaces).
** If a sensor is configured as Y (Connected) and is functioning properly, the display will show a reading.
If the connected sensor is not functioning properly, the display will show dashes (------) indicating a problem.
DEFAULT MAPPING OF DIGITAL INPUTS TO DIGITAL OUTPUTS (FROM TABLE 23)
Digital input By default, mapped to digital output:
Input_01 Output01
Input_02 Output02
Input_03 Output03
Input_04 Output04
Input_05 Output05
Input_06 Output06
Input_07 Output07
Input_08 Output08
DEFAULT MAPPING OF ANALOG INPUTS TO DIGITAL OUTPUTS (FROM TABLE 24)
Analog input By default, mapped to digital output:
Sensor_1 (none)
Sensor_2 (none)
Sensor_3 (none)
Sensor_4 (none)
DEFAULT SETTINGS - DIGITAL OUTPUTS (FROM TABLE 25)
Feature Default Other Options
LABEL OUTPUT01 - OUTPUT08 Any name (up to eight characters)
NORM OPEN/CLOSE NO (Normally open) NC (Normally closed)