Liebert Universal Monitor Pager User Manual


 
System and Control Options
55
9.6 Setup System - Setup I/O Matrix
The Setup I/O Matrix menu allows you to configure the Universal Monitor’s digital and analog inputs
to trigger various actions in any or all of the 16 outputs—eight on the main board and another eight if
the optional Expansion Board is used. Each output can be set up to respond to more than one digital
or analog input, including the additional 16 inputs available via the optional Expansion Board.
Almost any mapping combination can be used. For example, you may
decide to trigger an action in Output03 when Input_01 goes into alarm,
or you might want to generate an action in Output04 when Sensor_1
High Setpoint goes into alarm.
To set up the mapping of inputs to outputs:
Log In and Choose Setup System
From the Main Menu, use the arrows
↑↓ to choose System and
Control, then press Enter (see 9.1 - Login for help).
Enter your password at the Login screen.
From the System and Control Menu, use the arrows
↑↓ to choose
Setup System, then press Enter .
Select Setup I/O Matrix
From the Setup System Menu, shown at right, use the arrows
↑↓ to
choose Setup I/O Matrix and press Enter .
Use the following instructions to set up the mapping of each digital
input or analog sensor input to each output.
9.6.1 Set Up Mapping for a Digital Input
Use the arrows ↑↓ to choose Map Input To Output from the Map
Input/Sensor Menu, and press Enter .
From the Select Input Menu, choose the input you want—for exam-
ple, Input_01—and press Enter .
Map Input to a Main Board Output
From the Select Outputs menu, select Map to Main Board if you
want to map the selected input to an output on the Universal Mon-
itor’s main board. These outputs are identified as Outputs 1-8.
On the Output Map screen, you may map the selected input to any
of the eight outputs (1-8)—or to more than one output, if desired.
The example at right shows Input_01 mapped to Output03.
To make changes to the mapping:
If needed, press Enter to advance to the position directly
below the output.
Use the arrows ↑↓ to choose Y (Yes - Mapped to this output) or
N (No - Not mapped), then press Enter .
Press Enter to advance to the next position where you want
to make a change.
Use the arrows ↑↓ to choose Y (Yes - Mapped to this output) or
N (No - Not mapped), then press Enter .
When finished, press Enter again.
Setup System Menu
SETUP INPUT
SETUP COMMON ALARM
SETUP SENSOR
> SETUP I/O MATRIX
↑↓=NEXT =SELECT
SETUP OUTPUT
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP EXP BOARD
Map Input/Sensor Menu
> MAP INPUT TO OUTPUT
MAP SENSOR TO OUTPT
↑↓=NEXT
=SELECT
Select Input
SELECT INPUT
> INPUT_01
INPUT_02
↑↓=NEXT =SELECT
INPUT_03
INPUT_04
INPUT_05
INPUT_06
INPUT_07
INPUT_08
INPUT_09
INPUT_10
INPUT_11
INPUT_12
INPUT_13
INPUT_14
INPUT_15
INPUT_16
INPUT_17
INPUT_18
INPUT_19
INPUT_20
INPUT_21
INPUT_22
INPUT_23
INPUT_24
Select Outputs
SELECT OUTPUTS
> MAP TO MAIN BOARD
MAP TO EXP BOARD
↑↓=NEXT
=SELECT
Output Map
1 OUTPUT MAP
1 2 3 4 5 6 7 8
N
N Y N N N N N
↑↓=Y/N =NEXT/END