Liebert Universal Monitor Pager User Manual


 
System and Control Options
58
9.7 Setup System - Setup Output
The Universal Monitor has eight outputs that may be configured indi-
vidually. If the optional Expansion Board is used, its additional eight
digital outputs may be renamed. The outputs may have a wide variety
of Liebert or other manufacturers’ equipment connected for configured
responses to input alarms and events.
To configure an output:
Log In and Choose Setup System
From the Main Menu, use the arrows
↑↓ to choose System and
Control, then press Enter (see 9.1 - Login for help).
Enter your password at the Login screen.
From the System and Control Menu, use the arrows
↑↓ to choose
Setup System, then press Enter .
Select an Output to Configure
From the Setup System Menu, shown at right, use the arrows
↑↓
to
choose Setup Output and press Enter .
From the Select Output Menu, choose the output you want—for
example, Output01—and press Enter .
Table 25 shows digital output features and default settings. You may
change the name of any output. In addition, the Universal Monitor’s
eight outputs may be defined as normally open or closed.
Use the steps following Table 25 to change the default settings for any
digital output.
9.7.1 Change Label (Name of Output)
Each output has a default label (Output01, Output02, etc.) that you
may change to a more descriptive name. The label may consist of up to
eight characters (see Table 20 for valid characters).
From the Setup Output Menu, as shown at right, use the
arrows
↑↓ to choose Change Label for the selected output and
press Enter .
To change the output’s label, which may consist of up to eight char-
acters:
Use the arrows
↑↓ to choose a character.
Press Enter to advance to the next character position.
When finished, press Enter again.
9.7.2 Define Main Board Output as Normally Open / Closed
Each output may be set up as Normally Open (NO) or Normally Closed
(NC). The default setting for all output points is NO (Normally Open).
From the Setup Output Menu, choose Change State, as shown at
right, and press Enter .
To change the normal state for this output, use the arrows
↑↓ to
choose NO (Normally Open) or NC (Normally Closed), then press
Enter .
Table 25 Default settings - digital outputs
Feature Default Other Options
LABEL OUTPUT01
Any name (up to eight
characters)
NORM OPEN/CLOSE
(Main board only)
NO (Normally open) NC (Normally closed)
Setup System Menu
SETUP INPUT
SETUP COMMON ALARM
SETUP SENSOR
SETUP I/O MATRIX
↑↓=NEXT =SELECT
> SETUP OUTPUT
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP EXP BOARD
Select Output Menu
SELECT OUTPUT
> OUTPUT01 NO
OUTPUT02 NO
↑↓=NEXT =SELECT
OUTPUT03 NO
OUTPUT04 NO
OUTPUT05 NO
OUTPUT06 NO
OUTPUT07 NO
OUTPUT08 NO
OUTPUT09 NO
OUTPUT10 NO
OUTPUT11 NO
OUTPUT12 NO
OUTPUT13 NO
OUTPUT14 NO
OUTPUT15 NO
OUTPUT16 NO
NOTE: OUTPUT09-OUTPUT16
for optional Expansion Board
Setup Output Menu
> CHANGE LABEL
CHANGE STATE
↑↓=NEXT
=SELECT
Change Label
CHANGE LABEL
LABEL: OUTPUT01
↑↓=SELECT =NEXT/END
Setup Output Menu
CHANGE LABEL
> CHANGE STATE
↑↓=NEXT
=SELECT
Change State
SET TO NORMAL OPEN
OR NORMAL CLOSE? NO
↑↓=NO/NC =END