System and Control Options
53
9.5.9 Change Low Setpoint
The Low Setpoint value is typically above the 4 mA value for the sen-
sor. For example, if the 4 mA value is 50°F, the Low Setpoint might be
60°F. When the sensor crosses below this value, an alarm or event will
occur, depending on the sensor configuration.
The default Low Setpoint for each sensor is -950.0. Values that can be
entered range from:
• the 4 mA value + the Offset value (in the example, 50+5=55)
to
• the 20 mA value + the Offset value (in the example, 90+5=95)
To determine these values, see 9.5.4 - Change 4 mA Value, 9.5.5 -
Change 20 mA Value and 9.5.6 - Change Offset Value.
To enter a new value:
• From the Setup Sensor Menu, choose Low Setpt for the selected
sensor and press Enter ↵ .
• To change the Low Setpoint:
• Use the arrows
↑↓ to choose a character.
• Press Enter ↵ to advance to the next character position.
• When finished, press Enter ↵ again.
9.5.10 Change High Setpoint
The High Setpoint value is typically below the 20 mA value for the sen-
sor. For example, if the 20 mA value is 90°F, the High Setpoint might
be 85°F. When the sensor crosses above this value, an alarm or event
will occur, depending on the sensor configuration.
The default High Setpoint for each sensor is +950.0. Values that can be
entered range from:
• the 4 mA value + the Offset value (in the example, 50+5=55)
to
• the 20 mA value + the Offset value (in the example, 90+5=95)
To determine these values, see 9.5.4 - Change 4 mA Value, 9.5.5 -
Change 20 mA Value and 9.5.6 - Change Offset Value.
To enter a new value:
• From the Setup Sensor Menu, choose High Setpt for the selected
sensor and press Enter ↵ .
•To change the High Setpoint:
• Use the arrows
↑↓ to choose a character.
• Press Enter ↵ to advance to the next character position.
• When finished, press Enter ↵ again.
Setup Sensor Menu
SETUP SENSOR_1
CONNECTED : Y
LABEL: ROOM_TMP
↑↓=NEXT ↵ =SELECT
UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET: +005.0
ALARM/EVENT: AL
LATCHED: N
> LOW SETPT: +0055.0
HIGH SETPT: +0999.9
SENSOR DELAY: 00:01
Change Low Setpoint
CHANGE LOW SETPOINT
LOW SETPT: +0060.0
↑↓=SELECT ↵ =NEXT/END
Setup Sensor Menu
SETUP SENSOR_1
CONNECTED : Y
LABEL: ROOM_TMP
↑↓=NEXT ↵ =SELECT
UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET: +005.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0060.0
> HIGH SETPT: +0095.0
SENSOR DELAY: 00:01
Change High Setpoint
CHANGE HIGH SETPOINT
HIGH SETPT: +0085.0
↑↓=SELECT
↵ =NEXT/END