24 Freedom Sequence Intelligent Power Manager Owner’s Guide
Advanced Settings
Connect Sequence Delay
Reconnect-delay Timer The Freedom Sequence power manager applies
a reconnect-delay timer (Connect Seq Delay) before reconnecting an AC
circuit that was previously disconnected due to a load shedding event. In
other words, the reconnect-delay timer is applied before fully connecting to
the power source again.
The reconnect-delay timer, which can be modified by changing the
Connect Seq Delay, is set by default to ten seconds. The connect
sequence delay value applies to all AC relays and can be set between 4 to
60 seconds.
By default, the factory setting is set to 10 seconds.
Disconnect-delay Timer The disconnect-delay timer is programmed to
two seconds and cannot be modified. This means that after an overload
condition is detected, Freedom Sequence will wait for two seconds before
disconnecting the load circuit controlled through that relay.
To change the Connect Seq Delay from the Advanced Settings
screen:
FSPM 00: Status
L2 Amps
Batt Voltage
Circuit Status
Config
0.0A
12.8V
FSPM 00: Status
Batt Voltage
Circuit Status
Config
Advanced Settings
12.8V
FSPM 00: Advanced Settings
GEN BKR Rating
GEN Warmup Delay
Connect Seq Delay
AC Disc Priority
[30.0A]
[2sec]
[10sec]
[2]
FSPM 00: Advanced Settings
GEN BKR Rating
GEN Warmup Delay
Connect Seq Delay
AC Disc Priority
[30.0A]
[2sec]
[*10sec]
[2]
FSPM 00: Advanced Settings
GEN BKR Rating
GEN Warmup Delay
Connect Seq Delay
AC Disc Priority
[30.0A]
[2sec]
[5sec]
[2]
1 Press all three buttons to
enable Advanced Settings.
2 Scroll down to select
Advanced Settings.
5 Press to change
the setting.
6 Scroll up or down
to choose a value.
3 Press button.
7 Press to
confirm the
selected
value.
4 Scroll down
FSequence IPM Owners Guide.book Page 24 Thursday, October 6, 2011 3:33 PM