Xantrex Technology 809-0912 Wireless Office Headset User Manual


 
975-0593-01-01 19
Basic Configuration Settings
Load Shed
Load circuits controlled by AC-only relays can be forced to remain ON and
exempt themselves from the load shedding logic of the Freedom Sequence
power manager. This exemption technique is useful when you want to keep
one or two loads running at the expense of other loads in the system that
remain subject to the load shedding logic. If the Load Shed setting is
Disabled, this can be interpreted as rendering the load circuit “invisible”
from the power system. Thus, the power manager cannot apply the load
shedding logic to this circuit but can still apply to the other loads “visible”
to the power manager. Therefore, the user should be careful to change this
setting back to Enabled since this is not done automatically.
By default, the Load Shed setting of all the AC and DC relays is set to
Enabled.
To change the Load Shed from the Device Status screen:
FSPM 00: Status
L2 Amps
Batt Voltage
Circuit Status
Config
On 0.0A
12.8V
FSPM 00: Config
Mode
SHR BKR Mode
SHR BKR Rating
Circuit Config
[Operating]
[Manual]
[25.0A]
FSPM 00: Circuit Config
1 ACLoad1
1 Priority
1 Load Shed
2 ACLoad2
[2]
[Disabled]
FSPM 00: Circuit Config
1 ACLoad1
1 Priority
1 Load Shed
2 ACLoad2
[2]
[Enabled]
FSPM 00: Circuit Config
1 ACLoad1
1 Priority
1 Load Shed
2 ACLoad2
[2]
[*Enabled]
1 Press down until the
field is selected.
3 Scroll down until Circuit
Config is selected.
5 Scroll up or down to select a
load shed setting.
2 Press to activate
the screen.
4 Press to display
the screen.
7 Scroll up and down to
choose a value.
6 Press to
change.
8 Press to
confirm the
selected value.
FSequence IPM Owners Guide.book Page 19 Thursday, October 6, 2011 3:33 PM