Xantrex Technology 809-0912 Wireless Office Headset User Manual


 
975-0593-01-01 23
Advanced Settings
Generator Breaker Rating
The generator breaker rating can be set between 5 to 50 amps. By default,
the setting is set to 30 amps.
Generator Warmup Delay
The Freedom Sequence power manager applies a generator warmup delay
timer (GEN Warmup Delay) to allow any Xanbus-controlled generator a
chance to warmup after starting. This delay is similar to warming up a car
engine before driving.
The generator warmup delay timer, which can be modified by changing the
GEN Warmup Delay setting, is set by default to zero second. The generator
warmup delay timer value can be set between 1 to 240 seconds.
NOTE: It is recommended to set the GEN Warmup Delay value to match
either the transfer switch delay timer or the generator’s warmup delay timer
specified by the manufacturer of the device. Consult the device’s user guide
under its specifications or contact the manufacturer for information on the
timer rating. Choose a delay that is highest between these two devices.
To change the generator warmup delay from the Advanced Settings
screen:
FSPM 00: Status
L2 Amps
Batt Voltage
Circuit Status
Config
0.0A
12.8V
FSPM 00: Status
Batt Voltage
Circuit Status
Config
Advanced Settings
12.8V
FSPM 00: Advanced Settings
GEN BKR Rating
GEN Warmup Delay
Connect Seq Delay
AC Disc Priority
[30.0A]
[0sec]
[10sec]
[2]
FSPM 00: Advanced Settings
GEN BKR Rating
GEN Warmup Delay
Connect Seq Delay
AC Disc Priority
[30.0A]
[*0sec]
[10sec]
[2]
FSPM 00: Advanced Settings
GEN BKR Rating
GEN Warmup Delay
Connect Seq Delay
AC Disc Priority
[30.0A]
[2sec]
[10sec]
[2]
1 Press all three buttons to
enable Advanced Settings.
2 Scroll down to select
Advanced Settings.
5 Press to change
the setting.
6 Scroll up or down
to choose a value.
3 Press button.
7 Press to
confirm the
selected
value.
4 Scroll down
FSequence IPM Owners Guide.book Page 23 Thursday, October 6, 2011 3:33 PM