37
Network Configuration Quick Start
Figure 10: DN Setup / Index Sel (Predef)
4. Download this file to the Ei-DN.
5. Proceed to “Master Configuration” on page 48 before going any farther with this
example. After configuring the master return to this point and continue.
The following will initiate motion.
While Online with both the Ei-DN via PowerTools FM and the PLC via RSLogix 500:
6. Set Output Bit O:1.2/7 high to software enable the drive.
7. Set Output Bit O:1.1/0 high to initiate Index 0.
8. Set Output Bit O:1.1/1 high to initiate Home.
9. Set Output Bit O:1.1/2 high to Jog +.
10. Set Output Bit O:1.1/3 high to Jog -.
11. Set Output Bit O:1.1/4 high to enable Jog Fast.
12. Set Output Bits O:1.1/12 - O:1.1/15 to select the index to initiate or to select the index to
read from or write to using the Input/Output Word Select Data Pointer.