Low Volts Disconnect
Low Voltage Disconnect disconnects the batteries (Battery Disconnect) or the load (Load
Disconnect), at the preset LVD disconnect voltage. This prevents damage to the batteries
due to excessive deep discharge. The LVD reconnects the batteries or loads after the AC
power is restored.
When configuring the LVD reconnect voltage, ensure that the expected open-circuit recovery
voltage of the discharged batteries does not rise above the LVD reconnect voltage.
Temperature Compensation
Temperature Compensation automatically varies the float voltage to cancel the effects of
increasing or decreasing ambient battery temperature.
As the ambient temperature of the batteries increases, the voltage required to maintain it in a
fully charged state decreases.
Enable Temperature Compensation to help maintain optimum battery capacity over a wider
temperature range, which in turn extends battery life.