Eaton Electrical SC200 Wireless Office Headset User Manual


 
DCTools Setup
Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.
IPN 997-00012-41D December 2006
6-3
DCTools Setup
For your chosen communications option, configure the communications settings, in DCTools
according to the table below.
Then check that DCTools communicates correctly.
Properties Direct Connection Ethernet
Comms Enabled True True
Protocol S3P S3P
Connect Using COM1 Local Network
S3P Address 0 0
Server IP Address 10.64.129.1 (See Note 1)
Server Port 14000
Telnet – Cleared
Note 1:
Allocated by network administrator
SM45 Ethernet Setup
Before an SM45 supervisory module can communicate over an IP network with DCTools, the
SM45 must be set up for Ethernet communications.
Use the front panel or DCTools for configuring the SM45 supervisory module for Ethernet
communications.
Setup of Ethernet communications requires the following:
The network administrator assigning a unique IP address to each SM45 supervisory
module to be connected to the IP network
Setting the assigned IP address for each SM45
Setting the net mask / subnet mask and gateway address for each SM45 as appropriate
To configure the SM45 for Ethernet communications using DCTools
1 From the DCTools System Summary (Home) screen, click the Configuration
hotlink and
then Communications
to display the Communications view.
2 Under Ethernet, enter the assigned IP address, subnet mask and gateway address.