A SERVICE OF

logo

2. Press CALIBRATE.
3. Press the number (1 to 8) of the selected temperature input to
be calibrated.
4. Enter the number required to offset the current temperature
reading so a correct reading is obtained.
•To program a positive offset number (up to +10 degrees),
enter the number on the keypad. The Model 1108 recites the
digits as they are pressed.
•To program a negative offset number (up to -10 degrees),
first press PAUSE. The unit responds with a “beep.” Next,
enter the number on the keypad. The unit recites the digits as
they are pressed.
5. Press ENTER. The Model 1108 responds:“Enter.”
NOTE
If you find that your calibration offset exceeds more
than + 5 or -5 degrees, other complicating factors
could be affecting normal operation of the Model
1108. Call Sensaphone, Inc. for technical assistance.
Sensaphone
®
Model 1108 User’s Manual
76