Chapter 3: Quick Start
19
Step 4: Set Temperature Limits
High and low temperature limits can be separately programmed
for each input that is configured as temperature. Limits can
range from –20
°
to +150
°
Fahrenheit, or from –30
°
to 65
°
Celsius. Default settings are: 10
°
F for low temperature and
100
°
F for high temperature. Do not set temperature limits too
close to normal room temperature, since minor fluctuations
could result in frequent and unnecessary alarm dialouts.
1. Press SET.
SET
#
2. Press TEMP LIMITS.
TEMP LIMITS
5
3. From the number keys, press a number (from 1 to 8) that
corresponds to the temperature input being programmed.
RECOGNITION
TIME
7
4
1
VOICE
REPS
2
8
INTERCALL
TIME
3
MAX CALLS
CALL
DELAY
CLOCK
TEMP LIMITS
5
CALIBRATE
6
The Model 1108 responds: “Enter low temperature
limit.”
4. Using the number keys, enter a value for low temperature
limit. The Model 1108 will recite the digits as they are
pressed. If a negative number is required, first press
PAUSE, then enter the number.
RECOGNITION
TIME
7
4
1
VOICE
REPS
2
8
0
ID NUMBER
POWER
9
INTERCALL
TIME
3
MAX CALLS
CALL
DELAY
CLOCK
LISTEN TIME
SOUND
TEMP LIMITS
5
CALIBRATE
6
5. Press ENTER.
ENTER
TONE
PM