Chapter 5: Alarm Programming
53
In another example, input 5 is configured as a temperature
input. The current temperature is 76 degrees. During a Status
Report:
• If disabled, the Model 1108 recites “Number 5—Off—
76 degrees—OK.”
• If enabled, the Model 1108 recites “Number 5—
76 degrees—OK.”
5.3 Input Recognition Time
The Input Recognition Time is the length of time an alert
condition must be present before a valid alarm exists and dial-
out is activated. This time period is programmable, from 0
minutes, 0 seconds (for immediate response) up to a period of
272 minutes, 0 seconds. If an alert condition begins and then
clears within the established Recognition Time, no dial-out will
occur. When an alert condition continues beyond the pro-
grammed Recognition Time, the Model 1108 initiates dial-out.
The default setting for Input Recognition Time is 0 minutes,
3 seconds.
5.3.1 Programming Input Recognition Time
1. Press SET.
SET
#
2. Press RECOGNITION TIME.
RECOGNITION
TIME
7
3. Press the number (1 to 8) of the selected input to be
programmed.
RECOGNITION
TIME
7
4
1
VOICE
REPS
2
8
INTERCALL
TIME
3
MAX CALLS
CALL
DELAY
CLOCK
TEMP LIMITS
5
CALIBRATE
6
The Model 1108 responds: “Enter minutes.”