Appendix A: Troubleshooting
91
b) Recognition time setting is too long.
a) Batteries are either incorrectly installed
or drained.
3. The Model 1108 does not recog-
nize power failure.
To verify proper battery function, unplug the
unit and verify continued operation using
batteries only. If unit ceases to function,
first try reinstalling the batteries. If this is
not successful, replace the batteries. Refer
to Chapter 2, Section 2.4 for complete
instructions.
Reprogram Recognition Time. Set the
Recognition Time to the minimum required
for a monitored condition to become a valid
alarm. If possible, test the condition by
deliberately creating an alert condition.
Refer to Chapter 5, Section 5.3.
a) Inputs for alarm are disabled.
4. The Model 1108 does not
recognize any alarm.
Enable the inputs for alarm. Refer to
Chapter 5, Section 5.2.
b) Programmed Recognition Time is too
long.
Reprogram Recognition Time. Set the
Recognition Time to the minimum required
before a valid alarm occurs. If possible, test
the condition by deliberately creating an
alert condition. Refer to Chapter 5,
Section 5.9.