Chapter 5: Alarm Programming
53
In another example, input 2 is configured as a temperature
input. The current temperature is 76 degrees. During a Status
Report:
• If disabled, the Model 1104 recites, “Number 2—Off—
76 degrees—OK.”
• If enabled, the Model 1104 recites, “Number 2—
76 degrees—OK.”
5.3 Input Recognition Time
The Input Recognition Time is the length of time an alert
condition must be present before a valid alarm exists and dial-
out is activated. This time period is programmable, from 0
minutes, 0 seconds (for immediate response) up to a period of
272 minutes, 0 seconds. If an alert condition begins and then
clears within the established Recognition Time, no dial-out will
occur. When an alert condition continues beyond the
programmed Recognition Time, the Model 1104 initiates dial-
out. The default setting for Input Recognition Time is 0
minutes, 3 seconds.
5.3.1 Programming Input Recognition Time
1. Press SET.
2. Press RECOGNITION TIME.
3. Press the number (1 to 4) of the selected input to be
programmed.
The Model 1104 responds: “Enter minutes.”