Chapter 3: Quick Start
19
Step 4: Set Temperature Limits
High and low temperature limits can be separately programmed
for each input that is configured as temperature. Limits can
range from –20
°
to +150
°
Fahrenheit, or from –30
°
to 65
°
Celsius. Default settings are: 10
°
F for low temperature and
100
°
F for high temperature. Do not set temperature limits too
close to normal room temperature, since minor fluctuations
could result in frequent and unnecessary alarm dialouts.
1. Press SET.
2. Press TEMP LIMITS.
3. From the number keys, press a number (from 1 to 4) that
corresponds to the temperature input being programmed.
The Model 1104 responds: “Enter low temperature
limit.”
4. Using the number keys, enter a value for low temperature
limit. The Model 1104 will recite the digits as they are
pressed. If a negative number is required, first press
PAUSE, then enter the number.
5. Press ENTER.