Emerson iCOM IP Phone User Manual


 
Service Menu Parameters
67
COND PUMP-HIGH WATER CPH W Disabled, Enabled
LOSS OF FLOW LOF W Disabled, Enabled
STBY GLYCOL PUMP ON SGP W Disabled, Enabled
STANDBY UNIT ON STB W Disabled, Enabled
HUMIDIFIER PROBLEM HUP W Disabled, Enabled
NO CONNECTION w/Unit1 NOC W Disabled, Enabled
UNIT X DISCONNECTED - W Disabled, Enabled
LOSS OF POWER LOP W Disabled, Enabled
TYPE -- -
WORKING HRS EXCEEDED WHE W WRN
SMOKE DETECTED SMO W MSG, WRN, ALM
WATER UNDER FLOOR WUF W MSG, WRN, ALM
COND PUMP-HIGH WATER CPH W MSG, WRN, ALM
LOSS OF FLOW LOF W MSG, WRN, ALM
STBY GLYCOL PUMP ON SGP W MSG, WRN, ALM
STANDBY UNIT ON STB W MSG, WRN, ALM
HUMIDIFIER PROBLEM HUP W MSG, WRN, ALM
NO CONNECTION w/Unit1 NOC W WRN
UNIT X DISCONNECTED - W WRN
LOSS OF POWER LOP W MSG, WRN, ALM
Page 6 of 7
PASSWORD -W -
DELAY -- -
CUSTOMER INPUT 1 CI1 W 0 - 9999 sec
CUSTOMER INPUT 2 CI2 W 0 - 9999 sec
CUSTOMER INPUT 3 CI3 W 0 - 9999 sec
CUSTOMER INPUT 4 CI4 W 0 - 9999 sec
CALL SERVICE CS W 0 - 9999 sec
HIGH TEMPERATURE HTD W 0 - 9999 sec
LOSS OF AIR BLOWER 1 LB1 W 0 - 9999 sec
REHEAT LOCKOUT RL W 0 - 9999 sec
HUMIDIFIER LOCKOUT HL W 0 - 9999 sec
FC LOCKOUT FCL W 0 - 9999 sec
COMPRESSOR(S) LOCKOUT CL W 0 - 9999 sec
ENABLE - DISAB - - -
CUSTOMER INPUT 1 CI1 W Disabled, Enabled
CUSTOMER INPUT 2 CI2 W Disabled, Enabled
CUSTOMER INPUT 3 CI3 W Disabled, Enabled
CUSTOMER INPUT 4 CI4 W Disabled, Enabled
CALL SERVICE CS W Disabled, Enabled
HIGH TEMPERATURE HTD W Disabled, Enabled
LOSS OF AIR BLOWER 1 LB1 W Disabled, Enabled
Table 28 Set alarms parameters (continued)
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
SET
ALARMS