Emerson iCOM IP Phone User Manual


 
User Menu Parameters
52
Table 16 Set alarms parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
Page 1 of 1
Password PASSWORD W -
Return Sensor Alarms RTN SNSR W Enabled, Disabled
High Return Temperature HI TEMP W 34-210°F (1-99°C)
Low Return Temperature LO TEMP W 34-210°F (1-99°C)
High Return Humidity HI HUM W 1-99%
Low Return Humidity LOW HUM W 1-99%
Sensor A Alarms SENSOR A W Enabled, Disabled
High Temperature Sensor A HI TEMP A W 34-210°F (1-99°C)
Low Temperature Sensor A LO TEMP A W 34-210°F (1-99°C)
High Humidity Sensor A HI HUM A W 1-99%
Low Humidity Sensor A LO HUM A W 1-99%
Table 17 Sensor data
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
Page 1 of 2
Optional Sensor A Temperature TEMP A R 32-122°F (0-50°C)
Optional Sensor A Humidity HUM A R 20-80%
Optional Sensor B Temperature TEMP B R 32-122°F (0-50°C)
Optional Sensor B Humidity HUM B R 20-80%
Optional Sensor C Temperature TEMP C R 32-122°F (0-50°C)
Optional Sensor C Humidity HUM C R 20-80%
Freecooling Fluid Temperature FC TEMP R 4-113°F (-15 to 45°C)
Outdoor Temperature AMB TEMP R 4-113°F (-15 to 45°C)
Freecooling Status FC STATE R Off, Start, On, Blank
DigiScroll 1 Temperature DS1 TEMP R 84-313°F (29-156°C)
DigiScroll 2 Temperature DS2 TEMP R 84-313°F (29-156 °C)
Page 2 of 2
Daily High Temperature Hi Temp R 32-122°F (0-50°C)
Daily High Temperature
Hi Te H
Hi Te M
Hi Te S
R
-
Daily Low Temperature Lo Temp R 32-122°F (0-50°C)
Daily Low Temperature
Lo Te H
Lo Te M
Lo Te S
R
-
Daily High Humidity Hi Humi R 20-80%
Daily High Humidity
Hi Hu H
Hi Hu M
Hi Hu S
R
-
SET
ALARMS