Service Menu Parameters
57
Unit Diary—Large Display Only
Shows all entered program changes and maintenance performed on the unit.
VSD Setpoint VSD SET W 0-100%
Page 4 of 5
Password PASSWORD W -
VSD Fanspeed FANSPEED W Auto, Manual, Economy
VSD Setpoint STD VSD SET W
HPM: 30-100%
non HPM: 60-100%
VSD Setpoint MIN VSD MIN W
HPM: 30-100%
non HPM: 60-100%
VSD Setpoint Dehum VSD DEH W
HPM: 30-100%
non HPM: 60-100%
VSD Setpoint No Power VSD NOP W
HPM: 30-100%
non HPM: 60-100%
Page 5 of 5
Password PASSWORD W -
SCR Control Type CTRLTYPE W Tight, Standard, Economy
Start Compressor 1 At CO1 ON W -150 to +100%
Stop Compressor 1 At CO1 OFF W -200 to +50%
Compressor 1 Stop Delay CO1 TD W 0-30 min
Start Compressor 2 At CO2 ON W -150 to +100%
Stop Compressor 2 At CO2 OFF W -200 to +50%
Compressor 2 Stop Delay CO2 TD W 0-30 min
Cycle Time CYCLET R 0.2 – 200.0 sec
SCR Factor SCRFACT W 1.0 to 10.0
Actual SCR Request ACT SCR R 0-100%
Table 24 Unit diary parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
Page 1 of 1
Text entered with iST
(iCOM Service Tool)
N/A R -
Table 23 Setpoints parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
°C / °F
% RH
SET