Service Menu Parameters
58
See 3.9.1 - Calculation of Next Maintenance and Diagnostics for details on these menus.
Table 25 Standby settings / lead-lag parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
Page 1 of 1
Password PASSWORD W -
Number of Standby Units #STANDBY W
0-31
autocorrects to number
of connected units - 1
Rotation Frequency ROTATION W
No, Daily,
Mo-Tu-We-Th-Fr-Sa-Su;
(Monthly) M-Mo, M-Tu, M-We,
M-Th, M-Fr, M-Sa, M-Su
Rotate At (hour) ROT HOUR W 0-13
Rotate At (minute) ROT MIN W 0-59
Rotate By ROT BY W 1
Perform One Rotation DO ROT W No, Yes
Cascade Units CASCADE W No, Yes, Cooling, Cool/Heat
Start all Standby Units
by HT
STBY HT W No, Yes
Table 26 Maintenance / wellness settings parameters
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
Basic Settings (Page 1 of 8) WELLNESS BASIC
Password PASSWORD W -
Maintenance Frequency Per Year FREQ/YR W 0-12 per year
Max Bonus BONUS W 0-12
Max Penalty PENALTY W 0-12
Last Maintenance LAST PM W Date
Service Engineer SERVICE W Name
Confirm PM CONFIRM W No, Yes
Calculated Next Maintenance NEXT PM W Date
Motor Settings (Page 2 of 8)
Password PASSWORD W -
Number of Starts STARTS W 0-32000
Run Hours RUN HRS W 0-32000
Average Run Time AVG RUN W 0-999 min
Starts per Day Best BEST W 1-240
Starts per Day Worst WORST W 1-240
Number of Alarms ALARMS W 0-32000
Actual Bonus BONUS R 0-12
WELLNESS