Emerson iCOM IP Phone User Manual


 
Operation
32
3.7.3 Supply Limit—Optional
Chilled water units may be ordered with an additional sensor for monitoring the supply air tempera-
ture. This sensor maintains the minimum air temperature under a raised floor to help prevent con-
densation from forming. In order to avoid supply temperatures that are too low, the Supply Limit can
influence the opening of three-point or analog actuators or the output of analog values.
The control compares the deviation from the return air setpoint and the supply limit setpoint, and cal-
culates the output to the actuator from the smaller deviation.
3.7.4 High and Low, Temperature and Humidity Events
High- and low-temperature and humidity alarms can be set for both the internal and optional exter-
nal sensors. If a sensor reading exceeds a preset threshold, a warning will appear. These warnings are
ignored after unit startup for a minimum of 1 minute. To increase the delay to warn, see 3.7.6 -
Event Types and Properties. The threshold settings are located in both the User and Service
menus under Set Alarms.
To apply threshold limits on the internal cooling unit sensors, the Return Sensor Alarms must be
enabled. The high and low temperature and humidity internal sensor thresholds can then be set. To
apply threshold limits on the optional external sensors, the Sensor A alarms must be enabled. The
high and low temperature and humidity external sensor thresholds can then be set. If no external
sensors are connected to the unit, it is recommended that the Sensor A Alarms be disabled.
NOTE
The Supply Limit is calculated on each unit, independent of the other sensor readings on the
network.
NOTE
The event messages will automatically reset if the temperature/humidity stays 1.8°F
(1°C)/ 2% RH below or above the threshold for one minute.