Emerson iCOM IP Phone User Manual


 
Service Menu Parameters
66
ENABLE - DISAB - - -
COMP 1 OVERLOAD OL1 W Disabled, Enabled
COMP 2 OVERLOAD OL2 W Disabled, Enabled
COMP 1 HIGH PRESSURE HP1 W Disabled, Enabled
COMP 2 HIGH PRESSURE HP2 W Disabled, Enabled
COMP 1 LOW PRESSURE LP1 W Disabled, Enabled
COMP 2 LOW PRESSURE LP2 W Disabled, Enabled
COMP 1 PUMPDOWN FAIL PD1 W Disabled, Enabled
COMP 2 PUMPDOWN FAIL PD2 W Disabled, Enabled
DIG SCROLL1 HIGH TEMP HT1 W Disabled, Enabled
DIG SCROLL2 HIGH TEMP HT2 W Disabled, Enabled
EL HEAT HIGH TEMP EHO W Disabled, Enabled
TYPE -- -
COMP 1 OVERLOAD OL1 W MSG, WRN, ALM
COMP 2 OVERLOAD OL2 W MSG, WRN, ALM
COMP 1 HIGH PRESSURE HP1 W MSG, WRN, ALM
COMP 2 HIGH PRESSURE HP2 W MSG, WRN, ALM
COMP 1 LOW PRESSURE LP1 W MSG, WRN, ALM
COMP 2 LOW PRESSURE LP2 W MSG, WRN, ALM
COMP 1 PUMPDOWN FAIL PD1 W MSG, WRN, ALM
COMP 2 PUMPDOWN FAIL PD2 W MSG, WRN, ALM
DIG SCROLL1 HIGH TEMP HT1 W MSG, WRN, ALM
DIG SCROLL2 HIGH TEMP HT2 W MSG, WRN, ALM
EL HEAT HIGH TEMP EHO W MSG, WRN, ALM
Page 5 of 7
PASSWORD -W -
DELAY -- -
WORKING HRS EXCEEDED WHE W 0 - 9999 sec
SMOKE DETECTED SMO W 0 - 9999 sec
WATER UNDER FLOOR WUF W 0 - 9999 sec
COND PUMP-HIGH WATER CPH W 0 - 9999 sec
LOSS OF FLOW LOF W 0 - 9999 sec
STBY GLYCOL PUMP ON SGP W 0 - 9999 sec
STANDBY UNIT ON STB W 0 - 9999 sec
HUMIDIFIER PROBLEM HUP W 0 - 9999 sec
NO CONNECTION w/Unit1 NOC W internal
UNIT X DISCONNECTED - W internal
LOSS OF POWER LOP W internal
ENABLE - DISAB -- -
WORKING HRS EXCEEDED WHE W Disabled, Enabled
SMOKE DETECTED SMO W Disabled, Enabled
WATER UNDER FLOOR WUF W Disabled, Enabled
Table 28 Set alarms parameters (continued)
Function
Read/
Write
Range
Imperial (metric)
Large Display Small Display
SET
ALARMS