6.1.2 Weigand Test (1815, 1817 Systems Only)
This programming sequence will allow you to view the weigand data on the display as it is received
by the control board. This will allow you to verify that the weigand device is functioning properly.
1. Press *82 and enter the four-digit master code _ _ _ _ (beep).
2. Enter 9 9 9 9 * (beep).
3. Activate one of the weigand input devices by placing a card on a card reader,
pressing a transmitter button, or entering a digital code on a weigand keypad.
4. If the weigand data is shown on the display, this verifies that the weigand device is
operating properly and sending the information to the entry system. If no data
appears on the display, the weigand devices are not functioning.
5. Press 0# TOGETHER to cancel the weigand test mode.
6.1.3 Elevator Board(s) Hardware Test
This programming sequence is designed for trouble shooting the elevator control board(s) that may
be connected to the telephone entry system. This sequence will take approximately four (4) minutes
to complete and will check the operation of the CALL relay, and then all the odd numbered relays,
then all the even numbered relays on the elevator control board(s). This test confirms communication
between the telephone entry system circuit board and the elevator control board(s).
1. Press *76 and enter the four-digit master code _ _ _ _ (beep).
2. The display will show: WHICH ELEVATOR? (1815 - 1817 systems only).
3. Enter the elevator shaft number (1, 2, 3 or 4) _ then press * (beep).
The display will show: ELEVATOR TEST 1 (1815 - 1817 systems only).
Once the test starts, the CALL relay (LED ON) will activate, and then ALL odd
numbered relays will activate, and then ALL even numbered relays will activate on
the 1st elevator control board. After this sequence, if more than one elevator control
board is connected, ALL odd numbered relays, and then ALL even numbered relays
will activate on the 2nd elevator control board. After this sequence, ALL odd
numbered relays, and then ALL even numbered relays will activate on the 3rd
elevator control board. After this sequence, ALL odd numbered relays, and then ALL
even numbered relays will activate on the 4th elevator control board. This sequence
will repeat itself ten (10) times.
4. Once the test is complete (approximately 4 minutes), this programming sequence will
automatically end itself.
62