DKS Enterprises 1815 Telephone User Manual


 
2.2.3 Elevator Control Terminals
The elevator control terminals are used when the 2348-010 elevator control board is connected to the
system to enable elevator control. Do not connect any other devices to these terminals.
Maximum wire run for weigand data is 500 feet using Belden 9931, Consolidated 5324-CL, or
equivalent six (6) conductor shielded wire. Do not use twisted pair with weigand format. Float the
shield at the elevator control board. Do not connect the shield to the elevator board common.
If elevator control boards (2348-010) are being used with this system, refer to the Elevator Control
Installation and Wiring manual that came with the elevator control boards, for detailed information on
wiring these boards to the PC programmable telephone entry system.
2.2.4 RS-232 Terminals
The PC programmable telephone entry system may be programmed using the RS-232 serial
communication terminal. This terminal allows a direct connection to a computer using a standard DB-
9 serial connector on one end, and loose wires on the other that connect to the RS-232 terminals on
the board. You can order a 6-foot cable from DoorKing (P/N 1818-040), or make your own using the
wiring scheme shown below. A cross reference is also provided for a DB-25 connector.
TERMINAL DESCRIPTION
1 DATA 1 – to elevator control board terminal 20.
2 DATA 0 – to elevator control board terminal 21.
3 COMMON – to elevator control board terminal 22.
BOARD
TERMINALS
DB-9
PINS
DB-25
PINS
FUNCTION
1 3 2 Transmit Data
2 2 3 Receive Data
3 7 4 Request to Send
4 8 5 Clear to Send
5 5 7 Signal Ground - Shell
6 Not Used