26
Making detailed settings to the central control
unit(s), add-on control unit(s) or room sub
control unit(s)
NOTE:
Make the settings to the central control unit(s), add-on control
unit(s) or room sub control unit(s) respectively. You cannot select
multiple control units at the same time.
The following setting item buttons are displayed in the
“Advanced settings” window.
Click either the button
*
F
or
G
to open the
corresponding setting window, and then make the
settings in the displayed window(s). See the detailed
instructions for
F
or
G
below.
Click
*
Close
to close the current window and return to
the previous window.
F
Settings on [Contact input] window (for central
control unit(s) only)
Set the input method to each of the CONTACT INPUT
terminals.
Select the input terminal from S1 to S4 from the pull-
1
down menu.
[Contact type]:
2
Select either Normally open (NO) or Normally closed
(NC).
[Trigger condition]:
3
Select [None], [Broadcast chime] or [Stop chime] as
the trigger condition. When an input is detected, the
selected action is triggered.
[None]:
•
None will be triggered if an input is detected.
[Broadcast chime]:
•
Chime paging to the designated zone is triggered if an
input is detected.
[Stop chime]:
•
The currently-transmitted chime is stopped if an input is
detected.
Only when [Broadcast chime] is selected, the following
*
items are valid.
[Sound source]:
•
Select either [Internal sound source] or [External
sound source] as the source of chime. When [Internal
sound source] is selected, select a sound fi le or
sequence from the registered ones in the list.
(You need to register sound fi les (→P. 36) and/or
sound sequences in advance.)
When [External sound source] is selected, select
either “External sound source 1” or “External sound
source 2”.
[Chime priority]:
•
Select the priority of chime paging from among
“Normal”, “Priority” and “Urgent”.
[Zone name]:
•
Select the target zone of chime paging from the
registered ones in the list.
Repeat step
4
1 to 3 to make the settings to other
terminals.
Click
5
Close
to close the current window and return to
the previous window.
G
Settings on [Contact output] window
Set the trigger condition to each of the CONTACT OUTPUT
terminals.
Select an output terminal from the pull-down menu.
1
Select from L1 to L8 for the central control unit, and
*
select from L1 to L4 for the add-on control unit and room
sub control unit.
[Contact type]:
2
Select either Normally open (NO) or Normally closed
(NC).
[Trigger condition]:
3
Select the action as the trigger condition from among
the following. When the selected action is detected,
output is triggered.
[None]:
•
No output will be triggered.
[Calling notice]:
•
Set ON or OFF for “Normal”, “Priority” or “Urgent”.
[Door release]:
•
Select one of the registered sub stations in the list
to which an electric door strike is connected. (Click
Reference
, and then select the target station.)
[External sound source] (central control unit(s)
•
only):
Select either “External sound source 1” or “External
sound source 2” connected to the central control unit.
[PA output]:
•
Select from among “PA output 1” to “PA output 4”
connected to the control unit.
Repeat step
4
1 to 3 to make the settings to other
terminals.
Click
5
Close
to close the current window and return to
the previous window.
(central control unit(s) only)
F
G