APPENDIX A: SHIELD CONNECTOR INSTALLATION
This appendix provides the procedures for installing Scotchlok 4460 Shield Connectors, which
are manufactured by the 3M Company and utilized in the Fiber Management Panel. The shield
connector kit provides a means for grounding cables that have a metallic shield. Use the
following procedure to install each kit:
1. The shield connector kit is comprised of the components shown in Figure 34.
Figure 34. Kit Components
2. Prepare the cable by cutting the shield flush with the outer cable sheath as shown in Figure 35.
If the cable has a double sheath, cut only the outer sheath and shield leaving the inner sheath
intact as shown.
Figure 35. Cable Preparation
2 SECURING NUTS
TOP
BASE
9172-A
CORE
WRAP
CABLE
SHEATH
.75 IN. (19 mm)
SINGLE SHEATH CABLE
DOUBLE SHEATH CABLEDOUBLE SHEATH CABLE
.75 IN. (19 mm)
OUTER
SHEATH
INNER
SHEATH
CORE
WRAP
0.13 IN
(3mm)
9173-A