Omega OMA-P1104 Cordless Telephone User Manual


 
Chapter 5: Alarm Programming
63
7
RECOGNITION
TIME
3. Press POWER.
The OMA-P1104 will recite the power Recognition Time.
0
ID NUMBER
POWER
5.10 Sound Alarm Monitoring
This feature allows you to program the level and duration of
sound that will cause the OMA-P1104 to respond to an alarm
and dial-out. It may be useful to desensitize the OMA-P1104 to
sound if it is installed in an area with a relatively high noise
level, or where a loud noise occurs frequently but is not
associated with an alarm. In some applications, it may be
desirable to increase sound sensitivity to low sound levels.
5.10.1 Programming Sound Alarm Sensitivity
The sensitivity setting for sound alarm monitoring ranges from
1 to 255. A value of 1 makes the microphone the MOST
sensitive to changes in sound. The value 255 makes the
microphone the LEAST sensitive to sound. The default value
is 32.
1. Press SET.
SET
#
2. Press CALIBRATE.
6
CALIBRATE
3. Press SOUND. The OMA-P1104 responds: “Enter
number.”