Omega OMA-P1104 Cordless Telephone User Manual


 
Chapter 5: Alarm Programming
49
Chapter 5: Alarm Programming
This chapter explains the alarm programming and monitoring
capabilities of the OMA-P1104, with specific instructions for
the following features:
Configure inputs as dry contact or temperature
Enable/disable inputs
Program alarm Recognition Time for each input
Program high and low temperature limits
Disable alarm response to high or low temperature
Program temperature in Fahrenheit or Celsius scale
Calibrate temperature
Obtain current temperature
Program AC power-failure Recognition Time
Enable/disable AC power monitoring
Program sound level sensitivity
Program high sound Recognition Time
Disable alarm response to high sound
Use Exit Delay via Status Report
5.1 Input Configuration
In preparing the OMA-P1104 to sense an alert condition, the
inputs must be configured as dry contact (either open or
closed) or as temperature inputs. The default setting for input 1
is temperature; for inputs 2-4, the default is dry contact and
open. To configure input normality, sensors are first wired to
the terminal strip at the back of the unit. (Refer to Chapter 2,
Section 2.9–2.12, for an explanation on wiring inputs.)
The configuration process directs the OMA-P1104 to initialize
the 4 inputs and establish normal settings. Any change in the
status of an input (for example, from a normally open contact
to a suddenly closed contact) is recognized as an alert condi-
tion. In the case of a temperature input, an alert condition is
recognized when established temperature limits are exceeded.
NOTE
Before starting keyboard commands to configure input
normality on the OMA-P1104, it is very important to
check that the sensors you have wired to the unit are set
in their normal, non-alarm positions.