Omega OMA-P1104 Cordless Telephone User Manual


 
Omegaphone
®
OMA-P1104 User’s Manual
56
The OMA-P1104 responds: “Enter high temperature
limit.”
6. Using the number keys, enter the value for high tempera-
ture limit. The OMA-P1104 recites the digits as they are
pressed.
1
CALL
DELAY
2
VOICE
REPS
3
INTERCALL
TIME
4
MAX CALLS
5
TEMP LIMITS
6
CALIBRATE
7
RECOGNITION
TIME
8
CLOCK
9
LISTEN TIME
SOUND
0
ID NUMBER
POWER
7. Press ENTER. The OMA-P1104 responds: “Enter.”
ENTER
TONE
PM
ENTER
TONE
PM
NOTE
Do not set temperature limits too close to normal
room temperature. Minor temperature fluctua-
tions could result in frequent and unnecessary
alarm dialouts.
5.4.2 Disabling Alarm Response to High or
Low Temperature
To disable alarm response to either high or low temperature
settings exclusively, enter the maximum temperature limit when
programming the selected input. (The OMA-P1104 will not
respond to temperatures encountered at maximum settings or
beyond.) Begin by following the key sequence shown in
Section 5.4.1, and when prompted to enter the high or low
temperature value:
Set high temperature to either +150
o
F or +65
o
C (high
temperature limit) to prevent the OMA-P1104 from
responding to a high temperature alarm.
Set low temperature to either -20
o
F or -30
o
C to prevent